Definitionintro
Step response specifications
Also called time-domain specifications, transient response specifications.
The rise time, peak time, overshoot, settling time and steady-state value of the response to a unit step. Books differ on the rise time and the settling band, so a definition must state them.
Step response specifications are numbers read from the response of a stable system to a unit step input: how fast it rises, how far it goes past its final value, when it stays close to that value, and what the final value is. They state in the time domain what a closed loop must do, for example "overshoot at most 10 percent, 2 percent settling time at most 3 s, zero error to a step". Books do not agree on all definitions. The rise time is measured from 10 to 90 percent of the final value in some texts and from 0 to 100 percent in others, and the settling band is 1, 2 or 5 percent. So a specification is only complete when it says which definition it uses. This page fixes one set and gives the values for the standard second-order system and other examples.
Definition
Let be a rational transfer function whose poles are all in the open left half plane (so the system is asymptotically stable), with . Let be the output for the unit step input for , with zero initial state. Then , by the final value theorem. The specifications below are relative to ; take (otherwise use ).
- Steady-state value . For a closed loop from a reference to , the step error is ; see steady-state error.
- Rise time , where is the first time with . This page uses the 10 to 90 percent rise time. The 0 to 100 percent rise time is the first time with ; it exists only if reaches in finite time, which an overdamped response never does.
- Delay time , the first time the response reaches half its final value.
- Peak time , the time of the largest value , when that value exceeds .
- Overshoot , often given in percent. It is 0 when for all .
- Settling time for the band : the smallest such that for all . This page uses , the 2 percent settling time, unless it says otherwise.
- Undershoot , the largest move in the wrong direction.
Because has all poles in the open left half plane, decays exponentially, so exists for every and is finite. The other numbers are defined whenever their crossing times exist.
Formulas for the standard second-order system. For with , the exact values are , and the 0 to 100 percent rise time . The 10 to 90 percent rise time and the settling time have no closed form. The formulas and (2 percent band) are rules of thumb. The bound is exact, from the envelope of the response; the derivations are on the second-order system page.
Examples and non-examples
Example: a second-order system. For and rad/s:
| quantity | value | rule of thumb |
|---|---|---|
| overshoot | 0.16303 (16.3 percent) | |
| peak time | 3.6276 s | |
| rise time, 10 to 90 percent | 1.6376 s | s |
| rise time, 0 to 100 percent | 2.4184 s | |
| delay time | 1.2940 s | |
| settling time, 1 percent band | 8.7805 s | s |
| settling time, 2 percent band | 8.0763 s | s |
| settling time, 5 percent band | 5.2891 s | s |
The two rise times differ by almost 50 percent, which is why the definition must be stated.
Example: a first-order system. For , . There is no overshoot. The 10 to 90 percent rise time is , and the 2 percent settling time is . The 0 to 100 percent rise time does not exist.
Example: a third-order loop with a dominant pair. The unity feedback loop with and has the closed-loop poles (damping ratio 0.5, natural frequency rad/s) and . A simulation of its step response gives the overshoot 15.54 percent, the peak time 5.928 s and the 2 percent settling time 12.487 s. The second-order pair alone predicts 16.30 percent, 5.441 s and 12.114 s. The third pole is 7 times farther from the imaginary axis than the pair, and it still delays the peak by about 0.5 s; see root locus.
Example: a response with undershoot. has a zero at in the right half plane. Its step response is , which falls to at s before it rises to 1: an undershoot of 21.3 percent. A real zero in the right half plane always gives some undershoot (see minimum phase and complementary sensitivity function).
Example: the settling time can jump. For the second-order system with , the overshoot equals the 2 percent band when . Just below this value the first peak leaves the band and the settling time is about 5.07 s, which is the time the response re-enters the band after the peak. Just above it the response enters the band on the way up and stays there, and the settling time is about 3.60 s. So is not a continuous function of the parameters, and an optimizer that uses it as a cost must allow for this.
Non-example: an unstable or marginally stable system. For the step response is , which oscillates between 0 and 2 for ever. There is no final value and no settling time. The formula gives a number, but it is not a limit of .
Non-example: a system with zero gain at zero frequency. For , and . The relative numbers and the band are not defined. Such a response is described by its peak and its decay time instead.
Non-example: a rule of thumb used as a definition. "" is not the settling time of a third-order loop, nor even exactly that of a second-order system (8 s against 8.0763 s above). Use it only to place the poles in the first pass of a design.
Related definitions
- Steady-state error to a step, a ramp and a parabola, and the error constants; see steady-state error.
- Frequency-domain specifications. The bandwidth and the resonant peak of the complementary sensitivity function, and the phase margin of the loop, are the frequency-domain partners of the rise time and the overshoot. For the second-order system both sets follow from and .
- Regions in the s plane. For a dominant pair, means , and a settling time bound means a lower bound on . The root locus method places the dominant poles inside these regions.
- Integral criteria. The integral of the absolute error (IAE) or of the time-weighted absolute error (ITAE) of the step response measures the whole transient in one number; tuning rules such as those for the PID controller often minimize one of them.
- Impulse response. The step response is the integral of the impulse response, so the overshoot is zero when the impulse response is nonnegative.
References
- Katsuhiko Ogata, Modern Control Engineering, fifth edition, Prentice Hall, 2010, Chapter 5, Transient and Steady-State Response Analyses (the definitions of delay time, rise time, peak time, maximum overshoot and settling time, and their formulas for the second-order system)
- Gene F. Franklin, J. David Powell and Abbas Emami-Naeini, Feedback Control of Dynamic Systems, eighth edition, Pearson, 2019, Chapter 3, Dynamic Response (the time-domain specifications and the effects of zeros and extra poles)
- Karl J. Åström and Richard M. Murray, Feedback Systems, An Introduction for Scientists and Engineers, second edition, Princeton University Press, 2021, Chapter 6, Linear Systems (the step response and its specifications)