Also called cascade loop, master-slave control.

An inner loop controls a fast secondary variable and an outer loop sets its reference, so inner disturbances are rejected early.

Cascade control uses two feedback loops, one inside the other, with one actuator. The inner (secondary) loop measures a variable y2y_2 that the actuator moves quickly, such as a flow, a current or a speed, and holds it at a set point r2r_2. The outer (primary) loop measures the variable y1y_1 that really matters and computes r2r_2. A disturbance that acts on y2y_2 is then corrected by the fast inner loop before it reaches y1y_1. The inner loop also makes the outer loop see a simpler and more linear plant. The cost is a second sensor and a second controller to tune.

In plain words

Think of a room heated by hot water. The room temperature changes slowly, and the water flow changes fast. If the pressure of the water supply drops, a single temperature controller sees nothing until the room has already cooled. With cascade control, a fast flow controller keeps the flow at its target and fixes the pressure drop in seconds. The temperature controller does not move the valve itself; it only says which flow it wants. Each controller then has a simpler job. The inner loop must be clearly faster than the outer loop, and it is tuned first. A second sensor is needed, and it must see the disturbance that you want to remove early.

When it applies

  • A second measurement y2y_2 exists between the actuator and the main output y1y_1, so that the plant is a series y1=P1y2y_1 = P_1 y_2, y2=P2(u+d2)y_2 = P_2 (u + d_2).
  • P2P_2 responds clearly faster than P1P_1.
  • Important disturbances d2d_2 enter at the inner part, or the actuator is nonlinear (a valve, a motor), and the inner loop can hide this from the outer loop.
  • Classic cases: a temperature controller that sets the set point of a steam or coolant flow controller; a level controller that sets a flow; the position, speed and current loops of a motor drive.

The template

  1. Choose the inner variable. It should react to the actuator fast and should see the disturbances to reject.
  2. Tune the inner loop first, with the outer loop open. Often a P or PI controller with a high gain is enough, since a small offset in y2y_2 is corrected by the outer loop.
  3. Model the inner loop as closed. With the inner loop closed, the outer loop sees P1T2P_1 T_2, where T2=C2P2/(1+C2P2)T_2 = C_2 P_2/(1 + C_2 P_2). Often T2≈1/(τc2s+1)T_2 \approx 1/(\tau_{c2} s + 1).
  4. Tune the outer loop on P1T2P_1 T_2, for example with the SIMC rules or internal model control. A common rule of thumb asks for an inner loop 3 to 5 times faster than the outer loop.
  5. Handle the limits and the modes. If the inner loop saturates or is in manual mode, the outer controller must track the measured y2y_2 instead of its own output, or it winds up; see anti-windup. Close the inner loop first and open the outer loop first.

Why it works (theorem). Write S2=1/(1+C2P2)S_2 = 1/(1 + C_2 P_2) and T2=1−S2T_2 = 1 - S_2. From y2=P2(u+d2)y_2 = P_2(u + d_2), u=C2(r2−y2)u = C_2(r_2 - y_2) and r2=C1(r−y1)r_2 = C_1(r - y_1):

y2=P2S2d2+T2r2,y1=P1T2C11+P1T2C1r+P1P2S21+P1T2C1d2.y_2 = P_2 S_2 d_2 + T_2 r_2, \qquad y_1 = \frac{P_1 T_2 C_1}{1 + P_1 T_2 C_1} r + \frac{P_1 P_2 S_2}{1 + P_1 T_2 C_1} d_2.

Without the inner loop the factor S2S_2 is absent. So at the frequencies where the inner loop has high gain, ∣S2∣≪1|S_2| \ll 1 and the inner disturbance reaches the outer loop much reduced. A disturbance d1d_1 at the input of P1P_1 is not seen by y2y_2, and only the outer loop acts on it; there the gain from the cascade comes only from the faster outer loop that the simpler plant P1T2P_1 T_2 allows.

Classic examples

Two lags in series. Let P2=1/(s+1)P_2 = 1/(s + 1) (inner) and P1=1/(5s+1)2P_1 = 1/(5s + 1)^2 (outer), with a load d2d_2 at the input of P2P_2 and a load d1d_1 at the input of P1P_1. All controllers are PI with the SIMC rules and τc=θ\tau_c = \theta (Skogestad 2003).

  • Single loop on 1/((s+1)(5s+1)2)1/((s + 1)(5s + 1)^2). The half rule gives τ1=5+2.5=7.5\tau_1 = 5 + 2.5 = 7.5 and θ=2.5+1=3.5\theta = 2.5 + 1 = 3.5, so Kc=7.5/7=1.0714K_c = 7.5/7 = 1.0714 and Ti=7.5T_i = 7.5.
  • Inner loop on 1/(s+1)1/(s + 1) with τc=0.25\tau_c = 0.25: Kc=4K_c = 4, Ti=1T_i = 1, and T2=1/(0.25s+1)T_2 = 1/(0.25 s + 1) exactly.
  • Outer loop on 1/((0.25s+1)(5s+1)2)1/((0.25 s + 1)(5s + 1)^2): τ1=7.5\tau_1 = 7.5, θ=2.75\theta = 2.75, so Kc=7.5/5.5=1.3636K_c = 7.5/5.5 = 1.3636 and Ti=7.5T_i = 7.5.

Measured with a simulation step of 0.01 s, for unit steps:

structure set point: overshoot, settling time (2 percent) inner load d2d_2: peak of y1y_1, IAE outer load d1d_1: peak of y1y_1, IAE
single loop 0.088, 27.19 s 0.4485, 7.0 0.454, 7.0
cascade 0.092, 23.11 s 0.0146, 0.19 0.383, 5.5

The inner load is reduced by a factor of about 30 in peak, because the inner loop removes it early (the inner variable peaks at 0.157). The outer load is not seen by the inner loop, but the outer controller can be faster, and the IAE drops from 7.0 to 5.5. Both values equal Ti/KcT_i/K_c of the controller that has to absorb the load (7.5/1.0714 and 7.5/1.3636), which is the theorem on the integral of the error for a PI loop with a unit load and no change of sign of the error.

Variations

  • More than two levels. Motor drives often use three: current, speed and position.
  • P control in the inner loop. A P controller with a high gain is common in the inner loop; the outer integral removes the offset.
  • Feedforward into the inner loop. A measured disturbance can enter r2r_2 or uu directly; see feedforward control.
  • Parallel cascade. The disturbance or the actuator also acts on y1y_1 by a second path that does not pass through y2y_2. The design is similar, but the outer loop sees a different plant.
  • Ratio control. The inner set point is a measured flow times a ratio that the outer loop adjusts, a common structure in process control.

Pitfalls

  • An inner loop that is not faster. If the two loops have similar speeds, they interact, and the model of the inner loop as a simple lag no longer holds. Retune the outer loop slower or make the inner loop faster.
  • Wrong tuning order. Tuning the outer loop before the inner loop is closed, or tuning both loops with rules made for single loops without the inner loop model, can give an outer loop that does not converge. Tune the outer loop on P1T2P_1 T_2.
  • Windup of the outer loop. When the inner loop saturates, or is in manual, the outer integral keeps growing. Feed the measured y2y_2 back as the tracking signal of the outer controller, and limit r2r_2 to values that the inner loop can reach.
  • The wrong inner variable. If the main disturbance does not act on y2y_2, the cascade does little for it, as the outer load in the example shows.
  • Noise. A fast inner loop with a high gain amplifies the noise of y2y_2 onto the actuator.

Exercises

  1. Show that the PI controller Kc=4K_c = 4, Ti=1T_i = 1 on P2=1/(s+1)P_2 = 1/(s + 1) gives T2=1/(0.25s+1)T_2 = 1/(0.25 s + 1). (Answer: C2P2=4(s+1)/s⋅1/(s+1)=4/sC_2 P_2 = 4(s + 1)/s \cdot 1/(s + 1) = 4/s, so T2=4/(s+4)T_2 = 4/(s + 4).)
  2. Use the half rule on 1/((0.25s+1)(5s+1)2)1/((0.25 s + 1)(5s + 1)^2). (Answer: keep one time constant 5, add half of the second, τ1=7.5\tau_1 = 7.5; the delay is the other half plus 0.25, θ=2.75\theta = 2.75.)
  3. Derive the map from d2d_2 to y1y_1 in the cascade. (Answer: P1P2S2/(1+P1T2C1)P_1 P_2 S_2/(1 + P_1 T_2 C_1).)
  4. In the example, why is the IAE for the outer load 5.5 in the cascade? (Answer: the error has one sign, and its integral is Ti/Kc=7.5/1.3636=5.5T_i/K_c = 7.5/1.3636 = 5.5.)
  5. A temperature loop sets the set point of a steam flow loop. Which disturbance does the cascade remove early, a change of the supply pressure of the steam or a change of the inlet temperature of the product? (Answer: the supply pressure, because it changes the flow, which the inner loop measures.)

References

  1. Karl Johan Åström and Tore Hägglund, Advanced PID Control, ISA, 2006, Section 12.4, Cascade control
  2. Sigurd Skogestad, Simple analytic rules for model reduction and PID controller tuning, Journal of Process Control 13(4) (2003) 291-309, the whole paper (the half rule and the SIMC settings used in the example)

About this page

The build computes these levels from the evidence in the repository. Each row says what the next level needs. Read what the levels mean.

LadderLevelWhat the next level needs
Human proofH0 no proof
  • add a proof in proofs/ (06.5)
LeanL0 no Lean part
  • name a Lean module in the lean field (07)
VisualV0 none
  • add viz/scene.ts or a figure (10)
WritingW3 standard
  • five exercises