Relative gain array

Also called Bristol relative gain array.

A matrix of ratios of open-loop to closed-loop gains that tells which input should control which output in a multivariable plant.

The relative gain array (RGA) of a square plant with the gain matrix GG is the matrix

Λ(G)=G∘(G−1)T,λij=gij [G−1]ji,\Lambda(G) = G \circ (G^{-1})^T, \qquad \lambda_{ij} = g_{ij} \, [G^{-1}]_{ji},

where ∘\circ is the elementwise product. Bristol (1966) defined λij\lambda_{ij} as the gain from input uju_j to output yiy_i with all other inputs fixed, divided by the same gain when all other outputs are held constant by perfect control. If λij=1\lambda_{ij} = 1, closing the other loops does not change what uju_j does to yiy_i. The RGA is used to choose the pairing of inputs and outputs for a set of single loops, mostly with the steady-state gain G(0)G(0). It also flags plants that are hard to control: large elements mean that the plant is close to singular in a way that small errors in the model can change.

In plain words

A plant with several inputs and several outputs is often run with simple single loops: one controller per output, each moving one input. The question is which input goes with which output. The relative gain asks, for one input and one output: how much does this input move this output when the other inputs stay still, and how much when the other loops are closed and hold their outputs? If the two answers are the same, the other loops do not disturb this pair, and the pair is a good choice. If the second answer has the opposite sign, closing the other loops reverses the effect of this input, and the pair must not be used. Very large values warn that the plant is hard to control with any simple scheme.

When it applies

  • The plant is square, with nn inputs and nn outputs, and its gain matrix G(0)G(0) is known and nonsingular, for example from step tests.
  • Decentralized control (one single loop per output) is planned, and the pairing must be chosen.
  • A first check is wanted of how hard the plant is to control, before a multivariable design.
  • For dynamic questions, the same formula applies to G(jω)G(j\omega) at each frequency, mostly near the planned crossover.

The template

  1. Get the gain matrix G=G(0)G = G(0), or G(jω)G(j\omega) near the crossover.
  2. Compute Λ=G∘(G−1)T\Lambda = G \circ (G^{-1})^T. For 2×22 \times 2,
    λ11=11−g12g21g11g22,Λ=[λ111−λ111−λ11λ11].\lambda_{11} = \frac{1}{1 - \dfrac{g_{12} g_{21}}{g_{11} g_{22}}}, \qquad \Lambda = \begin{bmatrix} \lambda_{11} & 1 - \lambda_{11} \\ 1 - \lambda_{11} & \lambda_{11} \end{bmatrix}.
  3. Discard pairings with a negative steady-state element λij(0)<0\lambda_{ij}(0) < 0 (a theorem, below).
  4. Prefer pairings with elements near 1, mostly at the crossover frequency. This is a rule of thumb, not a theorem.
  5. Check the size. Large elements, say much larger than 1, mean that one pairing cannot avoid strong interaction and that the model must be very accurate. Consider decoupling or a multivariable controller.
  6. Tune and test the single loops, then test the full loop with all loops closed and with each loop opened.

Computing Λ\Lambda costs one matrix inverse, O(n3)O(n^3). Choosing a pairing is a choice among n!n! permutations, which is easy by enumeration for the small nn of practice.

Properties (theorems).

  • Rows and columns sum to 1. Since GG−1=IG G^{-1} = I, ∑jgij[G−1]ji=1\sum_j g_{ij} [G^{-1}]_{ji} = 1, and the same for columns from G−1G=IG^{-1} G = I.
  • Scaling does not change it. Λ(D1GD2)=Λ(G)\Lambda(D_1 G D_2) = \Lambda(G) for nonsingular diagonal D1D_1, D2D_2, so units do not matter.
  • Permutations. Swapping rows or columns of GG swaps the same rows or columns of Λ\Lambda.
  • Triangular plants. If GG is triangular, Λ=I\Lambda = I: the interaction runs one way only, and the diagonal pairing is free of it at steady state.
  • Meaning. With all other outputs held by perfect control, the gain from uju_j to yiy_i is 1/[G−1]ji1/[G^{-1}]_{ji}, so λij\lambda_{ij} is the ratio of the open-loop gain gijg_{ij} to this closed-loop gain.
  • Sensitivity to one element. If gijg_{ij} alone changes to gij(1−1/λij)g_{ij}(1 - 1/\lambda_{ij}), then GG becomes singular. Proof: det⁡G\det G is linear in gijg_{ij} with the cofactor CijC_{ij} as slope, and λij=gijCij/det⁡G\lambda_{ij} = g_{ij} C_{ij}/\det G, so the change −gij/λij-g_{ij}/\lambda_{ij} changes det⁡G\det G by −det⁡G-\det G. A large λij\lambda_{ij} means a small relative error makes the plant singular.
  • Negative elements (Grosdidier, Morari and Holt 1985). If a pairing has λii(0)<0\lambda_{ii}(0) < 0 and every loop has integral action, then at least one of these is not asymptotically stable: the full closed loop, loop ii alone, or the other loops with loop ii open.

Classic examples

The example of Skogestad and Postlethwaite. For G=[110.4−0.1]G = \begin{bmatrix} 1 & 1 \\ 0.4 & -0.1 \end{bmatrix} (their Example 3.9), g12g21/(g11g22)=0.4/(−0.1)=−4g_{12} g_{21}/(g_{11} g_{22}) = 0.4/(-0.1) = -4, so λ11=1/5=0.2\lambda_{11} = 1/5 = 0.2 and

Λ=[0.20.80.80.2].\Lambda = \begin{bmatrix} 0.2 & 0.8 \\ 0.8 & 0.2 \end{bmatrix}.

The off-diagonal pairing, u2u_2 with y1y_1 and u1u_1 with y2y_2, has elements 0.8, closer to 1.

A plant that is close to singular. For G=[87.8−86.4108.2−109.6]G = \begin{bmatrix} 87.8 & -86.4 \\ 108.2 & -109.6 \end{bmatrix}, λ11=1/(1−9348.48/9622.88)=35.07\lambda_{11} = 1/(1 - 9348.48/9622.88) = 35.07, and the other elements are −34.07-34.07. Both pairings are poor: one has the elements 35.07, the other negative elements. A change of g11g_{11} by 1/35.07=2.851/35.07 = 2.85 percent makes GG singular. The condition number of GG is 141.7, which tells the same story. Such a plant needs a multivariable design and an accurate model.

A negative element in practice. Let G(s)=G0/(s+1)G(s) = G_0/(s + 1) with G0=[1211]G_0 = \begin{bmatrix} 1 & 2 \\ 1 & 1 \end{bmatrix}, so λ11=1/(1−2)=−1\lambda_{11} = 1/(1 - 2) = -1 and λ12=2\lambda_{12} = 2. Pair on the diagonal with integral controllers k1/sk_1/s and k2/sk_2/s, with k1,k2>0k_1, k_2 > 0. Each loop alone has the characteristic polynomial s2+s+kis^2 + s + k_i, whose roots have negative real parts. With both loops closed the characteristic polynomial is

det⁡(s(s+1)I+G0diag⁡(k1,k2))=(s2+s+k1)(s2+s+k2)−2k1k2,\det\left(s(s + 1) I + G_0 \operatorname{diag}(k_1, k_2)\right) = (s^2 + s + k_1)(s^2 + s + k_2) - 2 k_1 k_2,

whose constant term −k1k2-k_1 k_2 is negative. A polynomial with a positive leading coefficient and a negative constant term has a positive real root, so the full loop diverges for every k1,k2>0k_1, k_2 > 0. The other pairing gives λ=2\lambda = 2 and det⁡(G0 with swapped columns)=1>0\det(G_0 \text{ with swapped columns}) = 1 > 0, and the constant term k1k2k_1 k_2 is positive.

Variations

  • Frequency-dependent RGA. Compute Λ(G(jω))\Lambda(G(j\omega)) over frequency. Elements near 1 at the crossover matter most for the interaction of the loops.
  • RGA number. The sum of ∣Λ−I∣|\Lambda - I| over the elements, for the chosen pairing as a permutation, gives one number to compare pairings over frequency.
  • Non-square plants. With the pseudo-inverse, the row sums show which outputs the inputs can control best, and they help to select outputs.
  • Block pairing. For blocks of inputs and outputs, a block RGA assigns groups to small multivariable controllers.
  • Decoupling. If no pairing is good, a decoupler DD with GDG D nearly diagonal is put before the single loops. This works only when the model is accurate, which the large RGA elements often deny.
  • Multivariable design. For plants with large elements, use model predictive control or H-infinity loop shaping instead of single loops.

Pitfalls

  • Steady state only. Λ(0)\Lambda(0) says nothing about the dynamics. A pairing that is good at steady state can interact strongly at the crossover.
  • Large elements are not fixed by a pairing. They show that the plant is close to singular. Inverse-based controllers on such a plant are very sensitive to errors in the input gains.
  • A singular gain matrix. If G(0)G(0) is singular, for example with integrating outputs, the RGA is not defined at s=0s = 0. Use G(jω)G(j\omega) at a low frequency or scale out the integrators.
  • Treating "near 1" as a guarantee. It is a rule of thumb. The full loop must still be checked, and the negative element test is the only part with a theorem behind it.
  • Model error. The RGA comes from a model; with large elements, a small model error can change even the signs.

Exercises

  1. Compute Λ\Lambda for G=[110.4−0.1]G = \begin{bmatrix} 1 & 1 \\ 0.4 & -0.1 \end{bmatrix}. (Answer: λ11=0.2\lambda_{11} = 0.2, so Λ=[0.2,0.8;0.8,0.2]\Lambda = [0.2, 0.8; 0.8, 0.2].)
  2. Show that each row of Λ\Lambda sums to 1. (Answer: ∑jgij[G−1]ji=[GG−1]ii=1\sum_j g_{ij} [G^{-1}]_{ji} = [G G^{-1}]_{ii} = 1.)
  3. Show that Λ=I\Lambda = I for an upper triangular GG. (Answer: G−1G^{-1} is upper triangular, so (G−1)T(G^{-1})^T is lower triangular, and the elementwise product keeps only the diagonal, with gii⋅1/gii=1g_{ii} \cdot 1/g_{ii} = 1.)
  4. For G=[87.8−86.4108.2−109.6]G = \begin{bmatrix} 87.8 & -86.4 \\ 108.2 & -109.6 \end{bmatrix}, which relative change of g11g_{11} alone makes GG singular? (Answer: −1/λ11=−1/35.07-1/\lambda_{11} = -1/35.07, a decrease of 2.85 percent.)
  5. In the negative element example, show that the full loop diverges for all positive gains while each loop alone converges. (Answer: the constant term of the characteristic polynomial is k1k2det⁡G0=−k1k2<0k_1 k_2 \det G_0 = -k_1 k_2 < 0, while each single loop has s2+s+kis^2 + s + k_i.)

References

  1. Edgar H. Bristol, On a new measure of interaction for multivariable process control, IEEE Transactions on Automatic Control 11(1) (1966) 133-134, the whole paper (the definition of the relative gain)
  2. Pierre Grosdidier, Manfred Morari and Bradley R. Holt, Closed-loop properties from steady-state gain information, Industrial and Engineering Chemistry Fundamentals 24(2) (1985) 221-235, the whole paper (negative relative gains and integral control)
  3. Sigurd Skogestad and Ian Postlethwaite, Multivariable Feedback Control, second edition, Wiley, 2005, Section 3.4, pp. 82-91 (the RGA, its properties and Example 3.9)

About this page

The build computes these levels from the evidence in the repository. Each row says what the next level needs. Read what the levels mean.

LadderLevelWhat the next level needs
Human proofH0 no proof
  • add a proof in proofs/ (06.5)
LeanL0 no Lean part
  • name a Lean module in the lean field (07)
VisualV0 none
  • add viz/scene.ts or a figure (10)
WritingW2 basic
  • three classic examples